Battery State of Charge (SoC) — How It Works

What services/battery_soc/battery_soc_mqtt.py does, why it computes the way it does, and which setting turns which screw. Supplements the general description in services/battery-soc.md and the installation steps in INSTALLATION.md.

Explicitly a monitoring/diagnostic estimate, not a BMS function. Do not use for automatic shutdowns without additional safeguards.

0. Architecture: Core + Adapter

The actual SoC math (coulomb counting, recalibration, load correction, the declarative entity list) lives transport-free in the stdlib-only package battery_soc_core — no paho-mqtt, no energy_node_common. battery_soc_mqtt.py is now only the thin MQTT adapter: it maps MQTT topics to SocInputs, calls engine.tick(), and translates the result (outputs dict + entity spec) into discovery configs and the /state payload. Simulation mode stays exclusively in the adapter — the core knows no substitute values.

A new number entity “Set manual SoC” (command topic outstation/<id>/cmd/manual_soc, or per bank in a series configuration .../cmd/manual_soc/bank_a and .../bank_b respectively) makes it possible to set the coulomb counter by hand to a known state of charge — useful when an installation rarely reaches the calibration thresholds (§3) during operation.

A future Home Assistant custom integration (separate plan) will use the same core as a second adapter without duplicating the domain logic.


1. The Installation and What Can Actually Be Measured

Two LiFePO4 banks hang on the same DC bus. A MeanWell charger charges, a Lumentree inverter discharges. What is measured:

Quantity Source What’s awkward about it
Charge power Shelly Plug S netz_meanwell measures the grid side, not the DC bus
Inverter power Shelly Plug S netz_lumentree also the grid side
Charge power DC (optional) Trucki T2MG DCPOWER already on the bus, no efficiency needed
Inverter power DC (optional) the Lumentree stick provides no DC value
Voltage bank A Shelly Uni genuine per bank
Voltage bank B Shelly Uni genuine per bank

There is no current sensor per bank. The bank current is always an estimate — hence the detour via power and voltage.

2. Coulomb Counting as the Basis

The actual SoC is an integrated charge counter (coulomb_ah per bank). Per cycle (default 10 s):

dc_charge_w    = max(0, charge_power)      * charger_ac_dc_efficiency
dc_discharge_w = max(0, inverter_power)    / inverter_dc_ac_efficiency
net_power_w    = dc_charge_w - dc_discharge_w      # positive = net charge

Why per converter and not once on the sum: both Shellys sit on the grid side, but the calculation happens on the DC bus. If only the charger runs, the difference is a constant factor. If both run at the same time — the normal case with ongoing consumption and simultaneous recharging — the two losses act in opposite directions, and a single factor applied to the already-formed net power is off by the maximum. Example with η = 0.9 per converter, 100 W charging and 50 W inverter:

Calculation path Result
wrong: (100 − 50) · 0.9 45.0 W
right: 100·0.9 − 50/0.9 34.4 W

The max(0, …) catches the small negative values that a Shelly Plug S reports when idle and that would otherwise inflate the division even further.

DC measurement takes precedence

If a *_dc_power_topic is configured and the last value is younger than dc_max_age_s (default 60 s), it replaces the AC measurement of that side without an efficiency factor — the value is already on the DC bus. Otherwise the AC path described above applies, with efficiency. Each side decides this independently: only the Trucki T2MG provides DCPOWER, the Lumentree stick has no DC value.

The net DC power is split across the banks (current_split_mode: capacity_ratio = in proportion to the nominal capacities, or equal = 50/50), converted to current per bank via the bank’s own voltage, and integrated:

delta_ah = current_a * dt_h * (charge_efficiency if charging, else 1.0)

charge_efficiency (0.98) is the coulombic loss inside the cell and something entirely different from the converter efficiencies above. On discharge it is 1.0: what flows out, flows out.

Why a split is defensible at all: it is only an assumption for the counter. Recalibration (§3) uses the real bank voltage and thereby corrects even a wrong split as soon as one bank reaches its end.

Protection against time jumps

An integration step longer than MAX_TICK_HOURS (1 h) or with a negative dt is discarded (dt_hours = 0). This guards against NTP corrections, suspend, and a stalled scheduler — without the guard, a single jump would be an arbitrarily large jump in SoC.

3. Recalibration at the Ends

LiFePO4 has such a flat voltage curve in the mid-range (~15–85 % SoC) that voltage is unusable there as a SoC source. Only near empty and near full does it change measurably. Exactly there — and only there — the coulomb counter is reset:

  • corrected cell voltage ≤ empty_v_per_cell (2.50 V) → counter to 0
  • corrected cell voltage ≥ full_v_per_cell (3.55 V) → counter to nominal capacity

Both only after the condition has held continuously for calibration_hold_s (120 s) (debounce against spikes). An intermediate value resets both timers.

So the counter does drift between two calibrations (measurement error, efficiency, self-discharge), but is caught again at each end.

4. Load Correction of the Voltage (“Voltage Curve Family”)

Under load the terminal voltage is not the resting voltage: too high when charging, too low when discharging. A naive comparison with full_v_per_cell would calibrate a charging bank to 100 % far too early. Instead of a curve family for every load current, the measured voltage is corrected by a current-dependent offset — mathematically equivalent, but with far fewer parameters.

Two ways, same meaning:

Default — bin table LOAD_OFFSET_TABLE_MV (mV/cell per C-rate):

C-rate up to Offset
0.05 5 mV
0.2 25 mV
0.5 60 mV
1.0 120 mV
above 200 mV

Optional — internal_resistance_mohm_per_cell: leave empty = table as before; set = linear Offset = I · R. If you work through the table, it is a constant resistance anyway (25 mV/20 A = 1.25 mΩ, 60 mV/50 A = 1.20 mΩ, 120 mV/100 A = 1.20 mΩ) — a single value is therefore the natural, measurable parameterization and at the same time continuous, whereas the table jumps at the bin boundaries (at exactly C = 0.2 by 35 mV, which on its own can already trigger a calibration).

Measuring: (voltage under load − resting voltage) / current / cell count. The value 0 explicitly means “no load correction” and is distinguishable from “not set”. At 0 A both ways yield the same value.

The corrected cell voltage is published as its own entity (“Load-corrected cell voltage bank A/B”). This is the number that makes the calibration decision — without it, neither the thresholds nor the internal resistance can be meaningfully re-tuned.

5. Calibration Telemetry and Tuning Suggestions

Every recalibration at the ends (§3) records an event with:

  • When it occurred (ISO timestamp)
  • How far the coulomb counter was off (residual)
  • How much charge and discharge the counter saw between this and the previous full calibration
  • The current at the moment the counter was caught
  • Whether the current held below the full_taper_c_rate threshold

These events form the basis for tuning suggestions on the two model parameters that actually matter: the inverter_dc_ac_efficiency (what fraction of DC power becomes AC), and indirectly the validation of the empty_v_per_cell threshold.

The three conditions of a reliable full-end calibration are:

  1. Corrected cell voltage ≥ full_v_per_cell (3.55 V)
  2. Current ≤ full_taper_c_rate × pack capacity (charging tail only, not bulk)
  3. The condition held continuously for calibration_hold_s (120 s)

Between two such calibrations, the pack was at both ends full: net charge over the interval is zero. Yet the coulomb counter recorded charged_ah in and discharged_ah out. This yields an equation:

a · charged_ah − b · discharged_ah = 0

where a and b are unknown correction factors. Two unknowns, one equation — only their ratio a/b is determinable, not the absolute values. This is not a weakness of the measurement but a property of a system with only one calibration anchor.

The way out is a reasoned normalization: the charge side is measured directly on the DC bus (charger_dc_power_topic) if configured, so a := 1. The discharge side has no DC measurement — the Lumentree stick provides none — and is estimated via inverter_dc_ac_efficiency from the grid side. That efficiency is the only free assumption, so the correction belongs exactly where the assumption sits:

inverter_dc_ac_efficiency_new = inverter_dc_ac_efficiency_old / (charged_ah / discharged_ah)

The algorithm proposes suggestions; it changes nothing. The service stays fail-closed. Applying a suggestion is a conscious action in the dashboard, the same way publish_allowed_prefixes are handled. With fewer than five intervals to work from, nothing is suggested at all — a single cycle is an anecdote, not a measurement series.

The capacity cannot be estimated from full-to-full intervals; it requires a full-to-empty path. Until a 0 % calibration is reachable (see roadmap), the algorithm reports this constraint and offers no capacity suggestion — fixing it requires different measurements, not tuning.

The threshold quality is a separate finding and does not come from the residual but from the state when the counter was caught: a calibration at 0.08 C is suspicious regardless of how small the residual was. A finding is reported if more than half of the recent full calibrations happened too close to the tail-current limit, pointing to a threshold that is too low (full_v_per_cell) or a tolerance that is too wide.

Internal Resistance Estimation from Calibration Behaviour

The raw (unload-corrected) pack voltage at a calibration anchor point, combined with the known anchor voltage and the current at that moment, yields an estimate of the internal resistance. At the anchor, the true open-circuit voltage equals the configured threshold (full_v_per_cell or empty_v_per_cell), regardless of which load correction model (bin table or internal_resistance_mohm_per_cell) brought it there. Therefore:

delta_v_per_cell = raw_v_per_cell − anchor_v_per_cell
R_i = delta_v_per_cell / current_a · 1000     [mΩ/cell]

Simulation with realistic sensor noise (±3 mV/cell, at the resolution limit of a Shelly Uni) shows the challenge: full-side calibrations occur only in the taper phase (full_taper_c_rate ≤ 0.05 C, i.e. ≤ 10 A on a 200 Ah system), small currents in the denominator amplify noise disproportionately, and single estimates scatter by 50–90 % of the true value. Empty-side calibrations have no taper condition (no equivalent to the full side’s tail-current requirement), yielding larger, less noisy currents. Because offset = I·R holds regardless of sign (unlike the directional bin table), both sides can be fused in a single estimate; doing so halves the scatter relative to the full side alone. Events with |current_a| below a minimum threshold (2.0 A) are excluded — the denominator is too small to distinguish signal from noise regardless of sample size.

7. Stale Inputs

If nothing arrives on a configured topic for longer than stale_input_s (120 s), the input is considered stale. Then integration and calibration are frozen:

  • Integration, because a charger Shelly that failed at 500 W would otherwise let the SoC keep rising without limit — the last measured value would just stay put.
  • Calibration, because the 120 s hold time could otherwise complete on pure stale data and wrongly set the bank to 100 %.

The currents are still computed and published (they are a display, not a state); only the counter stops.

Only configured inputs count. A topic left empty is not a fault but a statement — otherwise the warning would be permanently active in an installation with placeholder topics. stale_inputs in the state payload names the affected inputs in plain text, so the reason is visible without log access.

“Stale” has, since the DC extension, applied per input group, not per topic. The charge power, for example, is the group {DC topic, AC topic}: it is stale only when none of its topics is fresh. Otherwise “input data stale” would be permanently shown on every scheduled AC fallback (see above), even though the charge power is known throughout.

8. Single-Bank Installations

bank_b_enabled: false removes bank B from the current split, the total SoC, the imbalance, and the stale check; bank A receives the full current. All bank_b_* values in the payload become null and appear in Home Assistant as “unknown”.

Discovery is deliberately not omitted: energy_node_common knows no way to remove discovery again, so toggling would leave orphaned HA entities behind. “Unknown” is more honest than an invented 50 %.

9. Input Topics and JSON Keys

Each of the four inputs is a pair *_topic + *_json_key. The key is optional:

Payload json_key Result
{"apower": 12.5} apower 12.5 ✔
26.8 empty 26.8 ✔ (first number in the raw text)
26.8 apower no value — payload is not an object
{"id":0,"apower":12.5} empty 0 — the first number in the raw text is the 0

The two bottom cases used to be completely silent: the input was never updated, went “stale” after 120 s, and nothing appeared in the log. Now there is exactly one warning line per topic and error reason with the topic, the expected key, the start of the payload, and the keys actually present; if the reason changes, it warns again.

There is no fallback from the key path to the regex path: whoever configured a key wants that key. Silently taking the first number in the raw text would again be a wrong value instead of a visible error. As a preventive measure, the dashboard form suggests the keys from the last payload — see the configuration editor in dashboard.md.

All six *_json_key have "" as their default, and that is not carelessness but a requirement: the dashboard stores a field that is empty or at its schema default as an omitted key (readNode() in config.page.js). “Explicitly empty” and “never set” are thus the same in the JSON. If a guessed manufacturer name stood there, “no JSON key” would be unreachable via the UI — and a topic with a bare numeric payload (which is how the Trucki sticks publish every field) would be silently discarded. That was exactly the case as long as charger_power_json_key and inverter_power_json_key were set to apower. Suggestions belong in the <datalist> from the real payload, not in the default.

10. Settings Overview

All in services/battery_soc/battery_soc_devices.json, schema alongside, editable as a form in the dashboard. Saving triggers outstation/battery_soc/config/reload.

Setting Default Effect
charger_ac_dc_efficiency 0.9 fraction of the measured grid power that arrives on the DC bus (MeanWell 0.88–0.92)
inverter_dc_ac_efficiency 0.9 fraction of the DC power that reappears on the grid side (Lumentree 0.90–0.93)
charger_dc_power_topic / _json_key (empty) optional DC-side charge power, replaces the AC measurement without efficiency when fresh
inverter_dc_power_topic / _json_key (empty) optional DC-side inverter power, same principle
dc_max_age_s 60 s how long a DC measurement counts as fresh before AC applies again
charge_efficiency 0.98 coulombic loss inside the cell, only when charging
battery_chemistry lifepo4 cell chemistry, so far only LiFePO4 — calibration thresholds and simulation curve assume it
current_split_mode capacity_ratio split across the banks, alternatively equal
empty_v_per_cell / full_v_per_cell 2.50 / 3.55 calibration thresholds (load-corrected!)
calibration_hold_s 120 s debounce before a calibration
internal_resistance_mohm_per_cell (empty) empty = bin table, set = linear I·R, 0 = no correction
stale_input_s 120 s when an input counts as stale
bank_b_enabled true false for single-bank installations
imbalance_warn_v 0.5 V threshold of the imbalance warning (≈ 60 mV/cell with 8 cells)
bank_*_cell_count / bank_*_capacity_ah 8 / 100 installation data, feed into C-rate and split
bank_*_voltage_scale 1.0 factor on the reported voltage (divider ratio at the Shelly Uni)
simulation_*   power substitute values in simulation mode when the real topics are silent (see below)

11. Published Entities

All from one JSON payload on outstation/battery_soc/state via value_template. Order as in entities(). The payload additionally carries charger_power_source / inverter_power_source ("dc" or "ac"), even if no dedicated entity exists for it:

Entity Unit Meaning
SoC bank A / B / total % state of charge, device_class: battery
Voltage bank A / B V raw measured
Voltage difference A/B V diagnostic for aging/imbalance
Net battery power W DC side, after efficiencies
Last calibration A / B timestamp when the counter was last caught
Input data stale ON/OFF at least one configured input is silent
AC fallback active ON/OFF one side has a DC topic but is currently using the AC measurement
Current bank A / B (estimated) A from power and voltage, not measured
Remaining capacity bank A / B Ah value of the coulomb counter
Load-corrected cell voltage A / B V the number behind the calibration decision
Banks imbalanced ON/OFF |ΔU| > imbalance_warn_v
Time to full / empty h unfiltered, jitters with the measurement
Set manual SoC (bank A / B in series) % number entity, sets the coulomb counter directly (see §0)

The time estimates arise from an unfiltered Shelly measurement; the service smooths nothing anywhere. As an order of magnitude they are useful, as a displayed value they jitter. Below 10 W net power and with stale inputs they return null.

12. Persistence, Simulation, Operation

  • Persistence: the coulomb counter and calibration timestamps live in state_file (/home/energynode/battery_soc/state.json), so a restart does not discard the counter value. Write/read errors are deliberately not fatal.
  • Simulation: via the master/slave switch (settings/simulation_active/set) the service computes with substitute values instead of real MQTT inputs; “stale” is then off by definition. Real measurements still take precedence here too: if a topic is delivering fresh data right now, it is used; only silent topics fall back to simulation_charger_power_w / simulation_inverter_power_w. Useful for checking the efficiency calculation when topics are silent: 200 W charging and 50 W inverter must give 200·0.9 − 50/0.9 = 124.4 W.

    The bank voltage is no longer a constant here but follows a normalized LiFePO4 resting-voltage curve between empty_v_per_cell and full_v_per_cell (flat middle section, just like the real cell) — the same load offset that corrected_voltage_per_cell() removes again in real operation is added to the resting voltage. This makes the simulation a closed loop: power fills the coulomb counter, the voltage follows the state of charge, and at the ends the same recalibration applies as in operation (§3).

  • Device coupling: its own HA device, linked via via_device under energy_node. The Trucki stick in turn points via via_device to this device — deliberately no discovery merge (see the Trucki section in device-services.md).

12a. Home Assistant Integration

A native custom integration custom_components/battery_soc/ runs the same battery_soc_core as a second adapter. The config flow (user + advanced steps) captures all ~40 parameters; there is one config entry per battery (normalized to the name via async_set_unique_id). A DataUpdateCoordinator recomputes the tick() on every state change of a configured source entity and additionally on a fallback timer, so that time-based calibration and coulomb integration keep running even with idle inputs. The state is stored in homeassistant.helpers.storage.Store — a reboot starts at 50 % SoC, there is no import of the MQTT service state. A battery_soc.set_state_of_charge service plus a number entity “Set manual SoC” form the calibration anchors. Simulation mode is not carried over — only real operation.

13. Tests

The pure SoC domain logic has its own test suite in the core package; the adapter now only covers MQTT wiring, config loading, and golden-fixture parity:

.venv/bin/pytest libs/battery_soc_core/tests -v   # coulomb counting, calibration, entity spec, …
.venv/bin/pytest services/battery_soc/tests -v        # MQTT adapter + parity with pre-refactor behavior

Three tests are structural rather than behavioral checks and are worth mentioning:

  • test_schema_properties_match_dataclass_fields — catches “schema key added, dataclass field forgotten” in both directions. With additionalProperties: false plus BatteryConfig(**values) this would otherwise only surface as a hard reload error on the Pi.
  • test_*_entities_do_not_reference_missing_payload_keys — every value_key from entity_specs() must be present in the published /state payload. A typo in between is otherwise just a silent “unknown” entity in Home Assistant.
  • services/battery_soc/tests/test_core_parity.py — drives a scenario matrix (parallel/series, fresh/stale, simulation, …) through the core + adapter and compares /state and discovery configs byte-for-byte with the golden/*.json fixtures recorded before the core extraction. A deviation there is a real behavior change, not a test artifact.